The RNFP-LM floor-standing terminal circulates room air through a chilled- or hot-water coil. Its exposed cabinet sits at floor level for straightforward access.
وحدة لفائف المروحة الدائمة على الأرض
نظرة عامة
The vertical surface-mounted fan coil unit is a floor-standing room terminal for a central chilled- and hot-water system. Its finished cabinet remains visible within the occupied space, making it useful where a concealed ceiling installation is impractical or where access to the equipment is a priority.
Inside the cabinet, a fan circulates room air through a water coil. Cooling operation removes room heat and can collect condensate, while a suitable hot-water supply provides heating. The external finish is intended to coordinate with normal interior decoration.
The catalogue describes the RNFP-LM form as a unit that can be positioned directly on the indoor floor, with convenient dismantling and servicing. Installation planning should keep the inlet and discharge clear and provide practical routes for the water pipes and condensate drain.
تفاصيل المنتج
ميزات المنتج
Visible finished cabinet
The exposed casing receives an electrostatic coating and forms part of the room finish. It avoids the need to construct a complete ceiling enclosure around the terminal.
Floor-standing arrangement
The upright form can be located within the occupied room rather than suspended above it. Positioning is coordinated with circulation routes, furniture and the intended direction of conditioned airflow.
Water-based seasonal operation
A copper-tube coil exchanges heat with the circulating water. The selected central system supplies chilled water for cooling or hot water for heating according to the building’s operating arrangement.
Efficient finned coil
Mechanically expanded aluminium fins are closely coupled to the copper tubes. This construction provides an extended heat-transfer surface within a compact room terminal.
Low-noise fan assembly
A matched centrifugal fan and motor circulate air through the cabinet and coil. Selecting an appropriate operating speed helps balance room airflow, thermal duty and acoustic requirements.
Accessible routine maintenance
The cabinet can be opened for inspection and cleaning. Accessible filters, water valves and drain connections simplify routine service when the installation leaves adequate clearance around the unit.
بيانات النموذج
المواصفات الفنية
RNFP fan-coil family · vertical exposed arrangement. Catalogue pages 47–48, 49–50, 51–52.
Swipe tables horizontally to view all specifications.
| Model family | Airflow H / M / L (m³/h) | Cooling, H (kW) | Heating, H (kW) | Water flow (kg/h) |
|---|---|---|---|---|
| RNFP-34 | 340 / 260 / 170 | 1.8 | 2.7 | 319 |
| RNFP-51 | 510 / 390 / 260 | 2.7 | 4.05 | 478 |
| RNFP-68 | 680 / 510 / 340 | 3.6 | 5.4 | 638 |
| RNFP-85 | 850 / 640 / 430 | 4.5 | 6.75 | 797 |
| RNFP-102 | 1020 / 770 / 510 | 5.4 | 8.1 | 956 |
| RNFP-136 | 1360 / 1020 / 680 | 7.2 | 10.8 | 1275 |
| RNFP-170 | 1700 / 1280 / 850 | 9 | 13.5 | 1594 |
| RNFP-204 | 2040 / 1530 / 1020 | 10.8 | 16.2 | 1913 |
| RNFP-238 | 2380 / 1790 / 1190 | 12.6 | 18.9 | 2232 |
| Model family | Power at 12 / 30 / 50 Pa (W) | Noise at 12 / 30 / 50 Pa, dB(A) | Supply |
|---|---|---|---|
| RNFP-34 | 36 / 43 / 48 | 37 / 40 / 42 | AC 220 V / 50 Hz |
| RNFP-51 | 50 / 57 / 64 | 39 / 42 / 44 | AC 220 V / 50 Hz |
| RNFP-68 | 60 / 70 / 81 | 41 / 44 / 46 | AC 220 V / 50 Hz |
| RNFP-85 | 74 / 84 / 97 | 43 / 46 / 47 | AC 220 V / 50 Hz |
| RNFP-102 | 93 / 105 / 114 | 45 / 47 / 49 | AC 220 V / 50 Hz |
| RNFP-136 | 130 / 151 / 169 | 46 / 48 / 50 | AC 220 V / 50 Hz |
| RNFP-170 | 147 / 169 / 204 | 48 / 50 / 52 | AC 220 V / 50 Hz |
| RNFP-204 | 183 / 206 / 243 | 50 / 52 / 54 | AC 220 V / 50 Hz |
| RNFP-238 | 221 / 245 / 291 | 52 / 54 / 56 | AC 220 V / 50 Hz |
| نموذج | A | B | Approx. weight (kg) |
|---|---|---|---|
| RNFP-34LM | 790 | 470 | 27 |
| RNFP-51LM | 940 | 620 | 32 |
| RNFP-68LM | 1020 | 700 | 33.5 |
| RNFP-85LM | 1140 | 820 | 36.5 |
| RNFP-102LM | 1250 | 930 | 39.5 |
| RNFP-136LM | 1450 | 1130 | 50.5 |
| RNFP-170LM | 1730 | 1410 | 62 |
| RNFP-204LM | 1930 | 1610 | 65 |
| RNFP-238LM | 2130 | 1810 | 68 |
H / M / L = high / medium / low speed. Performance is the catalogue’s RNFP family data; cabinet form and selected coil arrangement must be confirmed for the chosen product. Cooling: entering air 27°C dry bulb / 19.5°C wet bulb, entering water 7°C with a 5°C rise. Heating: entering air 21°C and entering water 60°C. Power and noise values are at high speed. Dimension letters refer to the selected model’s catalogue drawing.
حيث يعمل
التطبيقات
An option for offices, hotels, reception rooms and refurbishment projects that need a visible water-system terminal. It is particularly useful when the building has limited ceiling space but can accommodate a cabinet at floor level.
Keep the air inlet and outlet unobstructed. Confirm cabinet dimensions, room noise requirements, water duty and drain arrangements before fixing the final position.
أرسل متطلباتك →- Office rooms with accessible perimeter equipment positions.
- Hotel and guest accommodation using central chilled or hot water.
- Meeting and reception rooms where a ceiling void is unavailable.
- Existing buildings being adapted to a room-by-room water system.