Vertical Air Handling Unit

Home / Products /

Vertical Air Handling Unit

Vertical air handling equipment for plant rooms and floor-standing installations.

Vertical Air Handling Unit

Overview

The vertical air handling unit is a floor-standing air-treatment assembly for plant rooms and other locations where an upright cabinet suits the available space. Its vertical arrangement brings the filter, water coil and fan sections together while leaving the connection layout to be coordinated with the duct network.

A centrifugal fan moves air through the selected filter and heat exchanger. Chilled water provides cooling and dehumidification, and an appropriate hot-water supply provides heating. The required coil rows and fan duty are selected against the actual design conditions.

The catalogue provides several vertical models and coil configurations. Final dimensions depend on the selected thermal duty and arrangement, so room height, access direction and the available space for servicing are considered before the layout is fixed.

Vertical Air Handling Unit

PRODUCT DETAILS

Product Features

Upright floor-standing cabinet

The vertical form suits equipment areas with usable height and a limited plan arrangement. The cabinet position is coordinated with the building structure, pipe routing and duct connections.

Integrated air-treatment assembly

Filter, coil and fan sections form a central treatment path. This gives the designer one coordinated unit for the required air quantity and thermal duty.

Copper-tube water coil

The selected water coil exchanges heat between the building’s water circuit and the airstream. Catalogue coil arrangements allow duty to be reviewed for both conditioned-air and outdoor-air operation.

Centrifugal fan selection

The fan is chosen for the required airflow and the resistance of the downstream system. The pressure allowance includes filters, ducts, outlets and other selected accessories.

Insulation and drainage planning

An insulated cabinet and correctly arranged condensate disposal support cooling operation. A suitable drain trap, water-pipe insulation and protected connections form part of the installation.

Accessible inspection and cleaning

Filters and heat-transfer surfaces need periodic attention. The layout should leave practical access to the service side and avoid making the fan or coil inaccessible after the ductwork is installed.

MODEL DATA

Technical Specifications

RNJK-L vertical water-coil AHU · six-row coil catalogue data. Catalogue pages 21–22.

Swipe tables horizontally to view all specifications.

Airflow, Fan and Acoustic Data
Model reference Airflow (m³/h) External pressure (Pa) Fan power (kW) Noise dB(A) Weight (kg)
020L 2000 160 0.45 ≤60 110
030L 3000 160 0.55 ≤60 127
040L 4000 210 0.75 ≤62 146
050L 5000 210 1.1 ≤64 168
060L 6000 210 1.5 ≤64 193
070L 7000 210 1.8 ≤65 222
080L 8000 210 2.2 ≤66 255
0100L 10000 260 2.2 ≤66 294
0120L 12000 260 3 ≤67 338
0150L 15000 260 4 ≤68 390
0180L 18000 260 2.2 × 2 ≤68 468
0200L 20000 310 3 × 2 ≤69 560
0220L 22000 310 3 × 2 ≤70 672
0250L 25000 460 4 × 2 ≤71 806
0270L 27000 460 4 × 2 ≤72 967
0300L 30000 460 5.5 × 2 ≤73 1160
0350L 35000 460 5.5 × 2 ≤74 1390
0400L 40000 460 7.5 × 2 ≤75 1530
0450L 45000 460 11 × 2 ≤76 1836
0500L 50000 560 15 × 2 ≤77 2020
0600L 60000 560 15 × 2 ≤78 2120
Six-Row Coil Thermal Duty
Model reference Cooling, A/C duty (kW) Cooling, fresh-air duty (kW) Heating, A/C duty (kW) Heating, fresh-air duty (kW)
020L 14.15 28.02 20.27 40.14
030L 19.16 36.88 29.05 55.92
040L – 56.71 41.42 79.72
050L 34.63 66.66 48.27 92.91
060L 41.64 78.23 59.59 111.95
070L 49.78 95.82 71.12 136.89
080L 58.96 113.5 82.84 159.47
0100L 75.97 146.23 105.72 203.5
0120L 94.43 181.78 130.06 250.37
0150L 119.62 230.26 164.37 316.41
0180L 138.98 267.65 183.62 353.63
0200L 145.44 279.13 203.12 389.81
0220L 156.28 300.85 223.38 430.02
0250L 180.48 347.42 254.97 490.82
0270L 198.47 411.75 279.37 579.58
0300L 225.23 433.57 315.41 607.17
0350L 271.01 521.68 375.82 723.42
0400L 316.49 609.24 437.23 841.65
0450L 355.34 683.38 490.4 943.12
0500L 396.09 762.3 546.52 1054.82
0600L 478.71 920.15 660.15 1268.91

The printed performance table covers vertical / horizontal arrangements; these references identify the vertical layout. A/C duty and all-fresh-air duty are different catalogue conditions. A dash in the 040L cooling cell indicates an ambiguous source value requiring confirmation. Confirm the complete model code, coil rows, water conditions and installation drawing.

WHERE IT WORKS

Applications

Suitable for commercial and industrial buildings using centralized chilled- or hot-water systems. The upright form is particularly relevant where an equipment room can accommodate the required cabinet height and floor loading.

Confirm airflow, pressure, water temperatures, cooling and heating duty, connection side and access space. The final unit dimensions follow the selected model and coil arrangement.

Send Your Requirements →
  • Office and commercial plant rooms with centralized ducted supply.
  • Hotel or public-building air-conditioning systems.
  • Industrial areas needing water-coil air treatment.
  • Refurbishment where an upright equipment layout suits the available room.
Illustration of a double-height hotel lobby with lounge seating and tall windows
Hotel Lobbies Ventilation and thermal comfort for shared hospitality spaces.
Illustration of an open-plan office with lounge seating and exposed ceiling services
Open-plan Offices Air distribution for comfortable commercial workspaces.

PROJECT INQUIRY

Discuss This Equipment

Tell us about your equipment requirements and installation conditions.