Ceiling-Mounted Fresh Air Handling Unit

Home / Продукция /

Установленный на потолке блок обработки свежего воздуха

Ceiling-mounted treatment and distribution of outdoor air.

Установленный на потолке блок обработки свежего воздуха

Overview

The ceiling-mounted fresh air handling unit treats and distributes outdoor air from within a suspended-ceiling installation. Its compact horizontal arrangement keeps the main equipment above the occupied room and connects to the building’s ductwork, water circuit and drainage system.

A fan draws air through filtration and a water coil before it is supplied to the room network. The selected coil can cool and dehumidify incoming air or provide heating from hot water. This is an air-treatment terminal connected to external utilities, rather than a self-contained cooling plant.

The D-series catalogue includes several airflow sizes and coil arrangements. Selection considers the outdoor-air duty, duct resistance and ceiling depth together, with clear access to the filter, fan, coil and condensate connection.

Ceiling-Mounted Fresh Air Handling Unit

PRODUCT DETAILS

Product Features

Ceiling-mounted space use

The horizontal cabinet is suspended above the finished ceiling, reducing the amount of equipment occupying floor space. Ceiling structure and support points are checked for the selected unit.

Filtered outdoor-air treatment

A filter section removes incoming particulate contamination before the selected thermal treatment stages. The filter arrangement is coordinated with both air-quality needs and the available fan pressure.

Cooling and heating coils

Water-coil configurations are selected to meet the project duty. Cooling operation can also remove moisture when the coil conditions are suitable, with condensate collected and drained.

Ducted air distribution

The fan supplies air through connected ducts and room outlets. Airflow and external static pressure are chosen from the real system resistance rather than the nominal airflow alone.

Compact insulated construction

The ceiling series uses an integrated cabinet arrangement intended for concealed service spaces. Insulation and connection details are coordinated to limit unwanted heat exchange and surface condensation.

Practical installation access

The installation needs a level support arrangement, suitable condensate fall and a drain trap where required. Flexible connections and clear maintenance openings help prevent service loads from being carried by the casing.

MODEL DATA

Technical Specifications

RNJK-D ceiling air-handling series · four-row coil catalogue data. Catalogue pages 17–18.

Swipe tables horizontally to view all specifications.

Airflow, Fan and Acoustic Data
Model reference Airflow (m³/h) External pressure (Pa) Fan power (kW) Noise dB(A) Weight (kg)
010D 1000 150 0.25 ≤58 62
010×2D 2000 150 0.25 × 2 ≤60 86
015D 1500 210 0.37 ≤59 72
015×2D 3000 210 0.37 × 2 ≤61 107
020D 2000 230 0.45 ≤60 84
020×2D 4000 230 0.45 × 2 ≤62 128
025D 2500 250 0.45 ≤61 91
025×2D 5000 250 0.45 × 2 ≤63 149
030D 3000 290 0.75 ≤62 98
030×2D 6000 290 0.75 × 2 ≤64 167
035D 3500 270 0.8 ≤62 119
035×2D 7000 270 0.8 × 2 ≤64 195
040D 4000 300 1.1 ≤63 134
040×2D 8000 300 1.1 × 2 ≤65 224
050D 5000 320 1.5 ≤64 154
050×2D 10000 320 1.5 × 2 ≤66 240
060D 6000 390 1.8 ≤64 177
060×2D 12000 390 1.8 × 2 ≤66 320
070D 7000 390 1.8 ≤65 204
070×2D 14000 390 1.8 × 2 ≤67 370
080D 8000 440 2.2 ≤66 234
080×2D 16000 440 2.2 × 2 ≤68 425
Four-Row Coil Thermal Duty
Model reference Cooling, A/C duty (kW) Cooling, fresh-air duty (kW) Heating, A/C duty (kW) Heating, fresh-air duty (kW)
010D 5.61 10.26 10.64 19.46
010×2D 11.33 20.62 21.28 38.72
015D 8.58 15.98 15.68 29.21
015×2D 17.16 31.59 31.5 57.98
020D 11.88 21.74 21 38.43
020×2D 21.8 44.41 39.8 77.78
025D 14.41 26.52 24.92 45.87
025×2D 28.93 53.25 49.84 91.74
030D 18.59 34.01 30.94 56.61
030×2D 37.29 68.65 61.88 113.92
035D 20.79 38.04 35.28 64.55
035×2D 41.58 76.09 70.56 129.12
040D 23.76 44.01 40.32 74.68
040×2D 47.52 87.49 80.64 148.46
050D 28.16 50.83 49.28 88.94
050×2D 58.52 101.48 93.24 161.69
060D 34.32 63.18 62.83 115.67
060×2D 67.76 110.21 122.64 199.48
070D 39.49 72.26 69.41 127.01
070×2D 79.99 152.54 153.48 292.67
080D 46.53 85.14 81.68 149.46
080×2D 91.08 176.86 160.02 310.73

Model references follow the catalogue’s suspended ceiling arrangement. A/C duty and all-fresh-air duty use different operating conditions. Confirm the complete model, coil rows, water conditions, ceiling load and access requirements when selecting the unit.

WHERE IT WORKS

Applications

Suitable for offices, hotels, shops and other buildings where outdoor air needs treatment but floor-standing plant space is limited. It can serve a defined room group or ventilation zone through the selected duct layout.

Confirm ceiling clearance, lifting and service access, water duty, air resistance and drainage before ordering. Any electric heating, motor control or damper options are confirmed for the selected configuration.

Send Your Requirements →
  • Commercial ceiling voids with adequate depth and structural support.
  • Hotel corridors or service areas distributing treated fresh air.
  • Office and retail zones supplied through short or medium duct routes.
  • Renovation projects with accessible water and condensate connections.
Illustration of a restaurant dining room with window-side tables
Restaurants Air treatment selected around occupancy and the dining-room layout.
Illustration of an open-plan office with lounge seating and exposed ceiling services
Open-plan Offices Air distribution for comfortable commercial workspaces.

PROJECT INQUIRY

Discuss This Equipment

Tell us about your equipment requirements and installation conditions.

From cleaner air
to a better future.

官网询盘